General Information on Smoke Alarms
From 1.7.2007, Qld legislation made it mandatory for at least one smoke alarm to be fitted on each level in every Queensland residence, including rental properties, regardless of when built. The smoke alarm(s) can either be powered by battery only or hard wired by an electrician to a lighting circuit. Hard-wired photoelectric alarms (see below) should also have a ‘Lithium’ back-up battery which has a service life of 7-10 years, so the alarm will still function if there is a power failure.
Legislation also requires that any new home (including units/apartment/townhouse etc.) approved for construction from 1.7.1997, must have at least one hard wired smoke alarm (with a backup battery) on each level but more if required under the law. Note the difference here is that for new residences built from 1.7.97, the smoke alarm(s) must be hard-wired but for residences built prior to 1.7.97, owners can either have a hard wired or a battery only operated alarm. The fire prevention authorities recommend that where there is an accessible lighting power circuit, hard-wired photoelectric smoke alarms (preferably interconnected) be installed with a backup ‘Lithium’ battery. Lithium batteries should have a service life of 7-10 years. In some cases, where there is a concrete ceiling and no void, hard wired alarms can still be fitted by cutting into the concrete or using a PVC conduit so the wiring can be run from a light fitting to the alarm. The engagement of a licensed electrician will be necessary.
In addition, on 1.7.2007, Qld legislation specifically made provision for the owners of all residential rental properties to have a smoke detector/alarm installed and these must be cleaned and tested before the commencement of each new tenancy. These alarms can either be battery only operated or hard wired to a lighting circuit (see above re preference for hard wired photoelectric smoke alarms). Smoke alarms should be fitted and maintained to manufacturers’ recommendations and owners must check regularly accordingly to manufacturer’s instructions to ensure that they remain operational. It is recommended that the ideal position for a smoke alarm is just outside bedrooms and this would normally be in the hallway.
In all cases, you must seek the advice of a licensed electrician, so the best advice can be provided to you in relation to this matter.







All too often during our inspections we identify areas which are conducive to the collection of retained ground moisture near a structure. Elevated moisture levels are known to provide conditions favourable to Timber Pest activity, particularly termites, and it is vital that every effort be made to avoid these risks. The most common causes of retained ground moisture are inadequate surface water drainage, downpipes not connected to drainage outlets, no gutters in place for roofing areas, outlet pipes for air conditioners, relief and overflow valves for hot water cylinders, corroding and join leakages of gutters and downpipes, defective or incomplete flashing and plumbing for rainwater tanks leaking. These are all issues which can be, and should be rectified, if they are in existence at a property.







